| Input Characteristics |
Input
impedance: 1 MW, 20 pF Voltage Rating: 600 Vrms, CAT III |
| Volt/Amps/Hertz Display |
True-rms
voltage (ac+dc) Ranges: 5.000 V, 50.00 V, 500.0 V, 1250 V* Accuracy: ±(1% +10 counts) True-rms current (ac + dc) Frequency Crest Factor |
| Power |
Watts,
VA, VAR Reactive Power 1-phase and 3-phase, 3 conductor balanced loads Ranges: 250 W, 2.50 kW, 25.0 kW, 250 kW, 2.50 MW, 25 MW, 250 MW, 625 MW, 1.56 GW Accuracy: ± (2% + 6 counts) Total Power, ± (4% + 4 counts) Fundamental power PF Power Factor DPF Displacement Power Factor Hz frequency fundamental |
| Harmonics |
Volts,
Amps, Watts: Fundamental: V,A ± (3% + 2 counts), W ± (5% + 2 counts) Range: 2 to 31st Harmonic Accuracy: V,A ± (5% + 3 counts), W ± (10% + 10 counts) Range: 32 to 51st Harmonic Accuracy: V,A ± (15% + 5 counts), W ± (30% + 5 counts) Frequency of fundamental: Range: 40 Hz to 70 Hz Accuracy: ± 0.25 Hz Phase: Volt & Amps (between Fund & Harmonic) Accuracy: 2nd (±
3º) . . . 51st (± 15º) K-Factor (Amps & Watts): THD: |
| Sags and Swells Recording |
Recording
times (selectable): 4 min to 16 days Vrms actual, Vrms max, min (AC+DC): Arms actual, Arms max, min (AC+DC): |
| Recording |
Recording
times (selectable) : 4 min to 16 days Parameters: Choose up to two from one of the groups below: V/A/Hz: Line voltage, current, frequency Power: Watts, VA, VAR, PF, DPF, frequency Harmonics: THD, volts(Fund. & Harmonics), Amps (F&H) Watts (F&H)
Freq. (H),%(H) of total, Phase(H), KF Ohms: Ohms, Diode, Continuity, Capacitance Temperature: °C or °F Scope: DC voltage, DC Current, AC Voltage, AC Current, Frequency, Pulse Width + or -, Phase, Duty cycle + or -, Peak max, Peak min, Peak min-max, Crest Factor |
| Transients |
Minimum
pulse width: 40 ns Useful bandwidth input 1: DC to 1 MHz (with test leads TL24) Number of transients 40 Voltage threshold settings: 20%, 50%, 100%, 200% above or below
reference signal Reference signal: After START, the Vrms and frequency of the
signal are measured. From these data a pure sinewave is calculated as
reference for threshold setting. Vpeak min, Vpeak max at cursor: |
| Inrush Current |
Current
ranges (selectable): 1 A, 5 A, 10 A, 50 A, 100 A, 500 A, 1000 A Inrush times (selectable): Cursor readings Time between cursors |
| Scope, dual channel scope with measurement reading |
Input
impedance Input 1: Input 2: Vertical Voltage Ranges: Vertical sensitivity, resolution: Bandwidth input 1 (voltage): Bandwidth input 2 (current): Coupling: Horizontal TimeBase modes: TimeBase ranges: Sampling rate: 25 MS/s Record length (min/max samples): Trigger source: Trigger Mode: Connect-and-ViewTM: Pre Trigger: Measurement readings, per channel selectable: |
| Ohms, Diode, Continuity, Capacitance |
Ohms: Ranges: 500.0 W, 5.000 kW, 50.00 kW, 500.0 kW, 5.000 MW, 30.00 MW Accuracy: ±(0.6% + 5 counts) Diode voltage: Continuity, shorts > 1 ms: Capacitance:
Temperature:* * Max current, max open circuit volt: |
| Memory | Number of screens: 20 |
| Optical Isolated RS-232 Interface |
To
printer: Supports HP LaserjetTM, Deskjet, Epson FX/LQ and Postscript printers with optional PAC91 Printer Adapter Cable To PC: FlukeView® Power Quality Analyzer Software with PM9080 Interface Adapter included |
| FlukeView Power Quality Software |
Hardware
requirements: PC or 100% compatible with Windows® 95, 98, Me, 2000, NT 4.0. |
| General Specifications | |
| Power |
Line voltage
adapter/battery charger included Installed battery: Rechargeable NiCd pack (4 to 6 Vdc) Operating time: 4 hours Charging time: 4 hours (Fluke 43B off) 12 Hours (Fluke 43B on) Refresh Cycle: 8 to 14 hours (to keep NiCd battery capacity optimal) |
| Environmental |
Temperature: 0 ºC to 50 ºC (32 ºF to 122 ºF) Environmental: MIL 28800E, Type 3, Class III, Style B Enclosure: IP51 (dust, drip water proof) |
| Mechanical Data |
Size: (H
x W x D) 232 x 115 x 50 mm (9.1 x 4.5 x 2 inches) Weight: 1.1 kg (2.5 lbs) incl. battery pack |
| Safety |
For
measurements on 600 Vrms Category III installations, Pollution Degree 2, in
accordance with EN61010-1 (1993) (IEC1010-1), ANSI/ISA S82.01-1994,
CAN/CSA-C22.2 No. 1010.1-92 UL3111-1 Surge protection: 6 kV on input 1 and 2 Floating measurements: 600 Vrms from any terminal to ground |
| Warranty | 3 years parts and labor on Fluke 43B, 1 year on accessories |